Photocoupler

Siemens S120 inverter alarm F07802 means that the power module is not ready: the power supply or power part is not ready, the specific reasons are:
May cause the cause -
1. The DC bus voltage has not reached the normal value;

2. The p0210 parameter value setting is not suitable and needs to be checked.

3. The power supply may be unstable;

4. The monitoring time is set too short, you can increase the monitoring time parameter p0857 appropriately.